Cable trays and the cable schedule

cheme layout build cables the plant when the repository has an electrical list (electrical/electrical-list.yaml, kind electrical). It derives the motor list, places the instruments and junction boxes, routes power and instrument cable trays through the 3D model and writes the cable schedule into layout/plant-model.yaml (tray_tiers, trays, junction_boxes, cables, cabling: layout-model.md). Skill electrical-cabling; gate requirements cables and trays.

Code: domains/control/schemas.py (ElectricalList), domains/control/electrical.py (motor list, cable sizes, instrument functions, actuated valves, the validate cross-checks), domains/control/data/cables.yaml (package table), domains/spatial/trays.py (ends, junction boxes, trays, schedule, rules), domains/spatial/schemas.py (TrayRules, the model sections). control declares, spatial places: spatial may import control (architecture.md).

Inputs

file kind what
electrical/electrical-list.yaml electrical (control) substations (id, building, incoming_kv), transformers (tag, substation, rating_kva, primary_kv, secondary_v, feeds), rooms (id, kind: mcc \| switchgear \| control \| rack_room, building or point, voltage_v), defaults (lv_room, mv_room, control_room, lv_voltage_v 400, mv_voltage_v 6600, mv_above_kw 200, jb_capacity 24, spare_pairs 0.2), motors (driven, tag, power_kw, voltage_v, room, assumed, source, skip, cable_entry: see Motor cable entry), feeders (tag, item or point, power_kw, ...), junction_boxes (tag, point or area, instruments patterns, capacity, room), instruments (tag, jb, point, skip)
electrical/tray-rules.yaml (optional) trays (spatial) rules: widths_mm (100 .. 900), depth_mm 100, fill_max_power 0.3, fill_max_instrument 0.4, separation_m 0.3, spacing_m 0.15, tier_gap_m 1.5, tiers: [{rack, elevation}], power_trays: [{rack, trays}] (below), lv_max_v 1000, lane_fraction 0.25, entry_elevation_m 3, branch_elevation_m 3, rack_reach_m 50, jb_elevation_m 1.2, jb_reach_m 30, termination_m 1.5, slack 0.05, grid_m 0.5, avoid_zones [oxygen_enriched, hazardous], support_span_m 6, support_reach_m 1. Every default ASSUMED
equipment/equipment-list.yaml, equipment/datasheets/<TAG>.yaml the driven items; their power (type_specific or operating: motor_kw, motor_power_kw, driver_kw, driver_power_kw, rated_power_kw, power_kw)
control/instrument-list.yaml, pid/*.xml the instruments; what each P&ID function measures (SensingLocation) and where it sits (Location: Field is a local gauge)

With an electrical list the model records it, the instrument list and the datasheets it took a power from as sources: a change outdates the model (layout-model-outdated).

Motors

Every equipment-list item whose DEXPI class ends in Pump, Compressor, Blower, Fan, Agitator, Mixer, Stirrer, Centrifuge, Conveyor, Crusher, Mill, Extruder, Kneader, AirCooledHeatExchanger, AirCooler or CoolingTower has a motor (M-<tag> unless motors names it), not a turbine, expander or engine, nor a machine of variant: compander | expander. Power: the motors entry, else the datasheet, else missing (electrical-motor-power, warning; the cable gets the smallest size and review_needed). Voltage: the entry's, else mv_voltage_v above mv_above_kw, else lv_voltage_v. Room: the entry's, else defaults.mv_room/lv_room, else the first switchgear (MV) or mcc (LV) room.

Cable sizes (package table, ASSUMED)

data/cables.yaml: a motor's full-load current P / (sqrt(3) U cos(phi) eta) with cos(phi) 0.85 and eta 0.92; a feeder's (heater, package) P / (sqrt(3) U cos(phi)) with its own power_factor (default 1.0, a resistive load, marked ASSUMED in the cable's basis; give it for a package with motors) and no efficiency. Both are three-phase: a single-phase load (a 230 V socket outlet) draws more for its power. The smallest size whose rating times the derating 0.8 carries it (LV 4-core 2.5 .. 300 mm2, MV 3-core 35 .. 300 mm2), else parallel cables of the largest; overall diameters typical of catalogues. A field instrument cable is 1 pair (transmitter, control valve) or 3 pairs (on/off valve), a junction box's home run the smallest multipair (2 .. 48 pairs) that holds its pairs plus spare_pairs. The table sizes the trays; it is no cable sizing.

Instruments and junction boxes

Cabled: every P&ID instrument function with a sensor that is not located Field, every instrument-list tag (drawn on no P&ID: needs a point), every in-line valve that is actuated (tag letters ending in V, not H.., ..SV, ..RV, ..CV; X, U, K, Z, SD, BD, ES, HS letters are on/off valves; or a DEXPI class with Control, Motor, Operated), and every instruments entry with a point; not those with skip. Position: the entry's point, else what the function measures (a nozzle's face, the middle of a routed segment, an in-line item, an item's centre up to 1.5 m), the valve's point. A device the model cannot place is listed under cabling.missing.

Junction box: the entry's jb, else the first box whose instruments patterns match, else the nearest declared box with a point within jb_reach_m and room left, else one proposed per site plan area (JB-<area>-<k>, the area's devices ordered by x, y and cut by jb_capacity) at their middle, jb_elevation_m up, moved to the nearest free spot (a 1 m ring search clear of items, steel, pipes): source: generated, review_needed. A field cable runs the orthogonal distance from the device to its box (not in trays).

Trays

Power cables (motors, feeders) and junction box home runs run in trays from their room:

  • Room exit: the room's point, else the middle of its building's side facing the nearest rack, 0.5 m out, at entry_elevation_m (rooms of one building 1.5 m apart along the side).
  • Rack path: the nearest rack within rack_reach_m of each end, the shortest way along the racks between them (racks join where their strips touch, as for the pipes). A cable whose ends reach no rack is fed directly (no rack in reach).
  • Trunk (kind: trunk, id PT|IT-<rack>-<k>): along the rack on its tray tier (a tiers rule, else tier_gap_m above the top pipe tier, carried by a generated tray_tiers entry: column extensions and a beam at each bent along the trunks' span), power trays lane_fraction x the rack width left of the centreline seen along the rack, instrument trays as far right. A trunk is cut wherever its set of cables changes.
  • Room (PT|IT-<room>), link (PT|IT-<rack>-<rack>, from one rack's lane onto the next at their joint) and branch (PT|IT-<load>): A* legs of the pipe router, clear of items, steel, walls, pipes and the trays before them by spacing_m; a branch runs at least branch_elevation_m high to above its load and drops onto it (0.6 m above the terminal box); a motor with a cable_entry ends its branch beside the item instead (below). Power trays and both trunks are routed first; instrument legs keep separation_m from every power tray. A leg the router cannot find is method: direct, review_needed.
  • Width: the smallest of widths_mm whose width x depth x fill_max holds the cables' cross-section; fill is cables' cross-section over the tray's.

Length of a cable: along its trays plus the drop to its terminal (route_length; the drop is orthogonal, from the tray's end to the terminal box), times 1 + slack, plus termination_m at each end, rounded up to the metre.

Several power trays per rack

A rack has one power tray unless power_trays gives it more: side by side on its tray tier, centred on the power lane, widths_mm[-1] + spacing_m apart centre to centre (1.05 m with the defaults), the first nearest the rack's centreline.

rules:
  power_trays:
    - {rack: PR-1, trays: 2}            # two trays, each takes any cable
    - {rack: PR-7, trays: [hv, hv, lv]}  # one voltage class per tray
field meaning
rack a rack of the site plan (once)
trays a count (1 .. 9; each tray takes any cable), or one class per tray: hv (cables rated above lv_max_v), lv (up to it) or any
lv_max_v (rule) the class limit, V (default 1000: the upper limit of low voltage in IEC 60038)

The build gives each power cable that runs on such a rack one of its trays, for its whole way along that rack (deterministic): the HV cables first, then the larger cross-section first, each into a tray of its class (else an any tray; else another, finding tray-voltage), among those the one that keeps its fullest piece along the cable's span under fill_max_power at the largest width, then the emptiest, then the first. Each tray is then cut and sized as a trunk of its own (id PT-<rack>-<A|B|...>-<k>) and checked for fill and separation like any tray. The room legs and links split with the trays they lead to (PT-<room>-<A>, PT-<rack>-<rack>-<AB>, the letters of the trays at each end; a rack's only tray has none); branches start at the cable's tray. The trays of a class record it (voltage: hv|lv); the cable schedule names each cable's trays. Without power_trays the model is unchanged.

Keeping cables above and below about 1 kV in separate trays (or apart by a fixed barrier) is common practice; the US National Electrical Code (NFPA 70, 392.20(B), see e.g. EC&M, "Mixing cables over and under 600V in cable tray") allows the two in one tray only with a solid fixed barrier between them or with the higher voltage cables of type MC. The project's electrical standard decides; power_trays only declares the trays.

Motor cable entry

Without it a motor's branch runs to above the terminal box and drops onto the machine, so the tray crosses the machine's footprint: a crane lane over the machine (cheme layout lifting) counts that tray as a blocker. A motor's cable_entry says where its cable leaves the tray beside the item; the branch ends there and the rest of the way to the terminal box is a cable drop (a conduit or a flexible cable, not tray), counted in the cable's length:

motors:
  - {driven: K-101, power_kw: 8567.9, cable_entry: {side: east, offset_m: 1.5}}
  - {driven: K-102, power_kw: 260, cable_entry: {point: [131.0, 152.0], elevation_m: 4.0}}
field meaning
side north (+y), south (-y), east (+x) or west (-x) side of the driven item's footprint in plan (the placed item's axis-aligned box in site axes)
offset_m along that side from its middle, m: toward +x on north and south, toward +y on east and west (default 0); at most half the side's length
clearance_m from the side out to the tray's centreline, m (default: the layout criteria's lane_margin_m + half the tray's width + spacing_m: just outside a crane lane that runs along that side or ends at it)
point instead of side: the tray's end [x, y], site m, outside the footprint
elevation_m the tray's end above grade, m (default 0.6 m above the terminal box); the branch runs at branch_elevation_m to above the entry and drops to it as tray

The branch's tray entry records the terminal box it drops to (drop_to); its last run is no longer the item's own drop, so the lifting lane and clash-tray count every run of it. Pick a side the lane runs along or the side away from the crane pad: an entry between the pad and the machine is still in the lane. A crane lane that runs diagonally to the footprint is wider than the footprint's sides: check with cheme layout lifting. The branch's way from the rack to the entry is the router's; it may still cross the lane higher up (the study names it).

cheme validate and cheme layout build: cheme.electrical-cable-entry (error, on the entry's line) when the placed item makes it impossible (a point inside the footprint, an offset_m beyond the side); the build then gives that motor no cable (cable-missing) rather than end the tray over the machine. The schema refuses an entry with neither or both of side and point, or with offset_m/clearance_m beside a point.

Rules (on the model)

rule level when
cheme.layout-tray-fill warning a tray's fill over its fill_max (only at the largest width); the hint names the power trays a rack's trunk needs (power_trays)
cheme.layout-tray-voltage warning a power tray of a class (voltage) carrying a cable of the other class (lv_max_v in cabling.rules): no tray of its class or any on the rack
cheme.layout-tray-separation warning a power and an instrument tray closer than separation_m (cabling.rules)
cheme.layout-clash-tray warning a tray through an item part (not the branch's drop onto its own item, unless the branch ends at a cable_entry), a pipe or a steel member
cheme.layout-tray-zone warning a tray inside a zone (layout/zones.yaml) of a kind in avoid_zones (cabling.rules; default oxygen-enriched and hazardous areas): move the lane, or record the cable sheath and glands for the zone and accept it
cheme.layout-tray-span warning a tray off the racks (no rack) with a level run longer than support_span_m between points where steel (rack, tray tier and structure members, enclosure walls, building wall panels and roofs) comes within support_reach_m of it
cheme.layout-cable-missing warning a motor, feeder, instrument or junction box without a cable (cabling.missing, with the reason)
cheme.layout-cable-unrouted warning a cable with a direct tray

cheme validate on the list: electrical-duplicate, -unknown-room, -unknown-substation, -unknown-tag (a motor's driven), -unknown-jb, -cable-entry (with the committed model; errors), -motor-power, -motor-room (warnings); layout-tray-rack for a tray tier or power_trays entry on a rack the site plan lacks or a rack listed twice in power_trays (errors), and for more power trays than fit on the power half of the rack at the largest width (warning).

Commands and gate

cheme layout cables [--csv | --json] [--write | --check]: the schedule of the committed model (Markdown: the cables, totals by size, the trays with width and fill, what has no cable); --write into electrical/cable-schedule.csv and .md, --check exits 1 when they are not current.

Gate kind: layout-model requirements: cables (an electrical list, a model with cables, no layout-cable-missing or -unrouted finding unaccepted) and trays (no layout-tray-fill, -separation or -voltage finding unaccepted). The template's detail-stage gate electrical requires [model-current, cables, trays].

Not modelled

Cable sizing (voltage drop, short circuit, protection, grouping), load flow, hazardous-area glands, earthing, lighting and small power, conduits and the field cables' own trays, tray supports other than the rack tray tiers, and the trays in the material take-off.