0035. A motor's cable entry ends its tray beside the machine

  • Status: Accepted
  • Date: 2026-10-30

Context

cheme layout build ran each motor's branch tray to 0.6 m above the terminal box and dropped it onto the machine, so the branch's last horizontal run lay over the machine's footprint. The lifting study's crane lane covers that footprint (the item's width across the direction of travel plus lane_margin_m each side, above its top plus lift_clearance_m). It left out only the branch's last vertical run, so the horizontal run blocked the lane. In the ammonia-1 run (process-library#304, cheme 1.0.1) this blocked the lanes of the compressors K-101, K-102, K-103 and K-701, and gate lifting-study failed (core#73). A project had no way to say where a motor's cable comes in, so the route could not be steered off the machine.

Options considered: a field on the motor entry of the electrical list; a field on the equipment placement (where the terminal box sits); leaving the tray as it was and not counting a motor's own tray in the lane. The electrical list is where a motor's cabling is declared, and an exemption would hide fixed steel over the machine from the lifting study.

Decision

  • The electrical kind (electrical/electrical-list.yaml) gives a motor an optional cable_entry: either side (north, south, east, west of the driven item's plan footprint, the placed item's axis-aligned box in site axes) with offset_m along it from its middle and clearance_m out from it, or point [x, y]. elevation_m is optional. The schema refuses neither or both of side and point, and offset_m or clearance_m with a point.
  • With it, the build ends the motor's branch at that point, at elevation_m (default 0.6 m above the terminal box, as without it). The branch keeps branch_elevation_m to above the point and drops to it as tray. The rest of the way to the terminal box is a cable drop, not tray. The cable's route_length includes it as the orthogonal distance. The default clearance_m is the layout criteria's lane_margin_m, plus half the tray's width, plus the tray rules' spacing_m.
  • The model's tray entry records the terminal box as drop_to (optional; only on such a branch). For a tray with drop_to, the lifting lane and clash-tray count every run. The exemption for the last drop onto the item applies only to a branch without one.
  • An entry the placed item makes impossible (a point inside the footprint, an offset beyond half the side) is cheme.electrical-cable-entry, an error on the entry's line in the electrical list (build, validate, layout report). The build gives that motor no cable (cable-missing) and does not end its tray over the machine.
  • Without cable_entry the build is byte-identical to before.

Consequences

  • Positive: a project can keep a crane lane over a machine clear of its own motor tray. The lifting study still names any tray that stands in the lane, including one beside the machine.
  • Positive: the cable schedule counts the drop, so its lengths do not shrink.
  • Negative: two new optional fields (motors[].cable_entry in the electrical list, trays[].drop_to in the model). Older readers that forbid unknown keys see drop_to only in models built with an entry.
  • Known limitations: the default clearance keeps the tray end outside a lane that runs along the chosen side or ends at it. A lane that runs diagonally to the footprint is wider, and an entry between the pad and the machine is inside the lane. The router chooses the branch's way from the rack to the entry, and that way can still cross the lane higher up. cheme layout lifting reports both cases. The cable drop has no geometry in the model.

Evidence

  • core#73; this PR.
  • src/chemeascode/domains/control/schemas.py (CableEntry), domains/spatial/trays.py (entry_problem, entry_point, cable_entry_findings), domains/spatial/engineering_rules.py (_lane), domains/spatial/schemas.py (ModelTray.drop_to).
  • tests/test_electrical_trays.py (test_a_cable_entry_ends_the_motor_tray_beside_the_machine, test_an_impossible_cable_entry_is_an_error_on_its_line).
  • docs/framework/electrical.md (Motor cable entry), skills electrical-cabling and structures-access.